UUT Calibration Setup
Communicate with the UUT
4
4-13
Table 4-2. UUT Personality Configuration Screen (cont.)
Item
Name
Description
Connection Type
Use to select the UUTs communication protocol. The communication
protocols available are:
•
TCP/IP
•
TCP/UDP
•
UDP
•
UDP Multicast
IP Address
Use to type in the IP address of the UUT. Typically, the UUT is
configured by the manufacturer with: 192.92.92.92
Port
Use to type in the UUT port number. Typical PMU port number is 4712.
ID
Use to type in the unique numerical identifier of the UUT. Each UUT
has unique numerical identifier in the UUT configuration. Refer to the
UUT users documentation for instructions on how to find out the UUT
ID number.
Version
The version of C37.118.2 communications protocol in use by the UUT.
Most UUTs use Version 2.
PMU Class
Use to set the class of the PMU. The PMU Class is determined by
internal settings of the PMU. Contact the PMU vendor to determine
internal settings to comply with M class or P class.
Nominal Voltage
Use to set the nominal voltage. Nominal voltage is determined by
internal settings of the PMU.
Nominal Current
Use to set the nominal current. Nominal current is determined by
internal settings of the PMU.
Voltage Input Ratio
Use to define the UUT voltage input ratio setting.
Current Input Ratio
Use to define the UUT current input ratio setting.
Settling Period
Settling period in seconds before a measurement starts.
System Output
Terminal Message
When a system contains a Fluke 6135A with either 50 A or 80 A
options or has Fluke 52120A Transconductance Amplifiers connected,
a message appears in this area that informs the operator which
terminals to use. This area is blank on a system with a standard Fluke
6135A.
Cancel
Use to cancel all changes.
Done
Close the dialog.
Connect to PMU and
get the PMU Config
Use to send a request to the UUT to get the UUT configuration
information. The UUT Phase Order tab opens with the UUT phase
order parameters loaded and ready to be set.
Save
Use to save the current PMU personality profile.
Load
Use to select and load a saved PMU personality profile.
Содержание 6135A/PMU
Страница 28: ...6135A PMU Operators Manual 2 2...
Страница 44: ...6135A PMU Operators Manual 3 2...
Страница 70: ...6135A PMU Operators Manual 3 28...
Страница 72: ...6135A PMU Operators Manual 4 2...
Страница 92: ...6135A PMU Operators Manual 4 22 gtu135 jpg Figure 4 12 Problem All Outputs Forced Off...
Страница 94: ...6135A PMU Operators Manual 5 2...
Страница 102: ...6135A PMU Operators Manual 5 10...
Страница 104: ...6135A PMU Operators Manual 6 2...
Страница 120: ...6135A PMU Operators Manual 7 2...
Страница 138: ...6135A PMU Operators Manual 7 20 gtu120 emf Figure 7 18 Example Report...
Страница 140: ...6135A PMU Operators Manual 8 2...
Страница 150: ...6135A PMU Operators Manual 9 2...
Страница 160: ...6135A PMU Operators Manual A 4...