The Fluke Calibration 6135A/PMUCAL Phasor Measurement Unit Calibration System
(the Product or Calibration System) is a measurement and calibration device used to
calibrate and test a PMU (Phasor Measurement Unit).
Features of the Calibration System:
•
Simulate static and dynamic conditions that a UUT can experience in a power grid.
•
Test a UUT against the performance standards written in
IEEE C37.118.1a- 2014
(Synchrophasor Measurements for Power Systems)
and
IEEE C37.118.2
(Synchrophasor Data Transfer for Power Systems)
and
IEC 60255-118-1:2018
(Synchrophasor for Power Systems - Measurements
.
•
Quickly set up and configure a UUT for calibration with a single, side mounted input
panel.
•
Remotely calibrate and test a UUT from a desktop PC using the PMU Calibration
Software.
•
Manually run single tests or use the factory built-in automated test procedures.
•
Produce formal calibration reports in a format that can be easily printed or shared
electronically.
The Calibration System is made up of six individual devices that are interconnected
inside a server rack (see Figure 1-1). See the “Components of the Calibration System” for
more information about each individual device.
The Fluke 6105A and two 6106A together comprise a 6135A. The Fluke 6135A is a
source of precision three phase voltage and current signals. These precise signals must be
related to Universal Coordinated Time (UTC) to be useful for calibration of PMU UUTs.
The 6135A/PMU System Timing Unit uses accurate time from the GPS receiver to align
the 6135A output frequency and phase angles to meet the requirements of the PMU
calibration standard:
IEEE C37.118.1a- 2014
.
A Client software application package on a laptop or desktop computer (not shown) lets
the operator communicate with the Server PC via a WAN (wide area network)
connection. The Server PC controls the equipment as required by calibration procedures
located on the Client computer.
For an alphabetical list of terms and abbreviations used in this chapter and manual, see
“The Glossary” in Appendix A of this manual.
About this Chapter
This Chapter supplies information about the Calibration System. Read this Chapter
before installing the Calibration System. For an alphabetical list of terms and
abbreviations used in this chapter and manual, see “The Glossary” in Appendix A of this
manual.
Содержание 6135A/PMU
Страница 28: ...6135A PMU Operators Manual 2 2...
Страница 44: ...6135A PMU Operators Manual 3 2...
Страница 70: ...6135A PMU Operators Manual 3 28...
Страница 72: ...6135A PMU Operators Manual 4 2...
Страница 92: ...6135A PMU Operators Manual 4 22 gtu135 jpg Figure 4 12 Problem All Outputs Forced Off...
Страница 94: ...6135A PMU Operators Manual 5 2...
Страница 102: ...6135A PMU Operators Manual 5 10...
Страница 104: ...6135A PMU Operators Manual 6 2...
Страница 120: ...6135A PMU Operators Manual 7 2...
Страница 138: ...6135A PMU Operators Manual 7 20 gtu120 emf Figure 7 18 Example Report...
Страница 140: ...6135A PMU Operators Manual 8 2...
Страница 150: ...6135A PMU Operators Manual 9 2...
Страница 160: ...6135A PMU Operators Manual A 4...