Verify that the contacts on the panel board are connected as intended
Note
Action
xx1500000803
Verify that the cables from the safety controller are
plugged into X1, X2, X5, and X6 on the panel board.
1
•
A: Contacts on the panel
board that must be connec-
ted with a cable to the
safety controller.
DANGER
If any of the contacts X1, X2, X5, or X6 on the panel board are jumpered, the
SafeMove functionality will not provide any safety.
Setting the configuration to validated
When the safety technician has validated the configuration and signed the safety
report, the status of the configuration shall be changed to
Validated
on the
FlexPendant.
Note/illustration
Action
See
Set up safety user grants on page 141
Log in as a user with the grant
Safety
Services
:
1
On the
ABB
menu, select
Log off
.
2
Tap
Yes
to confirm.
3
Select the safety user, type the
password and tap on
Login
.
1
On the
ABB
menu, tap
Control Panel
and
then
Safety Controller
.
2
xx1500000805
On the tab
Configuration
, select
Valid-
ated
.
3
Continues on next page
184
Application manual - Functional safety and SafeMove2
3HAC052610-001 Revision: P
© Copyright 2016-2020 ABB. All rights reserved.
6 Configuring SafeMove
6.20 Validate the configuration
Continued
Содержание SafeMove2
Страница 1: ...ROBOTICS Application manual Functional safety and SafeMove2 ...
Страница 2: ...Trace back information Workspace 20C version a3 Checked in 2020 09 14 Skribenta version 5 3 075 ...
Страница 8: ...This page is intentionally left blank ...
Страница 16: ...This page is intentionally left blank ...
Страница 34: ...This page is intentionally left blank ...
Страница 56: ...This page is intentionally left blank ...
Страница 72: ...This page is intentionally left blank ...
Страница 112: ...This page is intentionally left blank ...
Страница 194: ...This page is intentionally left blank ...
Страница 196: ...This page is intentionally left blank ...
Страница 234: ...This page is intentionally left blank ...
Страница 237: ......