Parameters 195
29.11
Reference step 6
Sets a percentage that is added to the process setpoint
when six auxiliary (direct-on-line) motors are running. See
parameter
0.00 … 100.00%
Reference step 6.
100 = 1%
29.12
Reference step 7
Sets a percentage that is added to the process setpoint
when seven auxiliary (direct-on-line) motors are running.
See parameter
.
0.00 … 100.00%
Reference step 7.
100 = 1%
30
30 Fault functions
Configuration of behavior of the drive upon various fault
situations.
30.01
External fault
Selects a source for an external fault signal.
0 = External fault trip
1 = No external fault
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
30.02
Speed ref safe
Defines the safe speed reference that is used with the
setting of supervision parameters
upon an
alarm. This speed is used when the parameter is set to
-30000 … 30000
rpm
Safe speed reference.
1 = 1 rpm
30.03
Local ctrl loss
Selects how the drive reacts to a control panel or PC tool
communication break.
No
No action taken.
0
Fault
Drive trips on fault
.
1
Spd ref Safe
The drive generates alarm
and sets the speed to the speed defined by parameter
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
Last speed
The drive generates alarm
and freezes the speed to the level the drive was operating at.
The speed is determined by the average speed over the
previous 10 seconds.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
30.04
Mot phase loss
Selects how the drive reacts when a motor phase loss is
detected.
No
No action taken.
0
Fault
The drive trips on fault
.
1
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...