Parameters 261
Const
Bit pointer setting (see
on page
-
Pointer
78.11
Interlock pump 6
Selects the input (or signal) for status of pump 6.
When the input is 1, the drive assumes the pump is in use
and can be started.
Not used
The interlock is off, meaning that the pump is not in use.
0
On
The interlock is on, meaning that the pump is ready for use.
1
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
78.12
Interlock pump 7
Selects the input (or signal) for status of pump 7.
When the input is 1, the drive assumes the pump is in use
and can be started.
Not used
The interlock is off, meaning that the pump is not in use.
0
On
The interlock is on, meaning that the pump is ready for use.
1
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
78.13
Interlock pump 8
Selects the input (or signal) for status of pump 8.
When the input is 1, the drive assumes the pump is in use
and can be started.
Not used
The interlock is off, meaning that the pump is not in use.
0
On
The interlock is on, meaning that the pump is ready for use.
1
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
78.14
Runtime change
Enables the reset, or arbitrary setting, of
.
No
The parameter automatically reverts to this value.
0
Set
Enables the setting of
to an arbitrary
value.
1
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...