278 Parameters
81.32
Pid enable dev
Defines the process actual value level at which the Pipefill
function is disabled and normal PID control is enabled. After
the level is reached, the time defined by parameter
is allowed to pass before normal PID control is
enabled. PID reference ramps are then observed (if set).
The value is given in percent of the maximum process actual
value.
0.00 … 100.00%
Pipefill / PID control breakpoint.
100 = 1%
81.33
Pid enb dev dly
Delay for enabling PID control. See parameter
.
0…12600 s
PID enable delay.
1 = 1 s
81.34
Pipefill timeout
Defines the maximum allowed time for the Pipefill function. If
the target process actual value (parameter
) is not reached within this time, the action defined by
parameter
is taken.
0…12600 s
Maximum Pipefill time.
1 = 1 s
81.35
Pipefill flt ctr
Defines the action for the Pipefill timeout (parameter
).
Alarm
.
0
Fault
.
1
Activate PID
Normal PID control is enabled.
2
82
82 Pump cleaning
Settings for the pump cleaning sequence.
See also section
on page
.
82.01
Pump clean trig
Enables the pump cleaning sequence for the drive, and
defines the triggering conditions.
WARNING!
Before enabling the pump cleaning
sequence, ensure it can be performed safely with the
connected equipment.
Notes:
• Multiple triggering conditions can exist simultaneously.
• The cleaning sequence observes the speed limits defined
.
• The drive must be started and its run enable signal
present before the cleaning sequence can be started.
No.
Name/Value
Description
FbEq
Time
Forward
Reverse
1
2
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...