![ABB ACQ810 Скачать руководство пользователя страница 218](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549218.webp)
218 Parameters
36.23
Timed func3
Selects which time periods (1…4) are used with timed
function 3. Also determines whether boost is used with timed
function 3.
The parameter is a 16-bit word with each bit corresponding
to a function. Whenever a bit is set to 1, the corresponding
function is in use.
The bits of the binary number correspond to the following
functions:
36.24
Timed func4
Selects which time periods (1…4) are used with timed
function 4. Also determines whether boost is used with timed
function 4.
The parameter is a 16-bit word with each bit corresponding
to a function. Whenever a bit is set to 1, the corresponding
function is in use.
The bits of the binary number correspond to the following
functions:
38
38 Flux ref
Flux reference and
U/f
curve settings.
See also section
on page
38.01
Flux ref
Sets the flux reference (in percent of parameter
) at field weakening point.
0 … 200%
Flux reference at field weakening point.
1 = 1%
38.03
U/f curve func
Selects the form of the
U/f
(voltage/frequency) curve below
the field weakening point.
Note:
This functionality can be used in scalar control only,
Linear
Linear
U/f
curve. Recommended for constant-torque
applications.
0
Quadratic
Quadratic
U/f
curve. Recommended for centrifugal pump
and fan applications.
1
User
Custom
U/f
curve. The curve is formed by the points defined
2
38.04
U/f curve freq1
Defines the frequency at the 1st point on the custom
U/f
curve in percent of parameter
.
1 … 500%
1st point, frequency.
1 = 1%
38.05
U/f curve freq2
Defines the frequency at the 2nd point on the custom
U/f
curve in percent of parameter
.
No.
Name/Value
Description
FbEq
Bit
Function
0
Timer1 ena (Time period 1 enable)
1
Timer2 ena (Time period 2 enable)
2
Timer3 ena (Time period 3 enable)
3
Timer4 ena (Time period 4 enable)
4
Boost ena (Boost enable)
Bit
Function
0
Timer1 ena (Time period 1 enable)
1
Timer2 ena (Time period 2 enable)
2
Timer3 ena (Time period 3 enable)
3
Timer4 ena (Time period 4 enable)
4
Boost ena (Boost enable)
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...