Parameters 219
1 … 500%
2nd point, frequency.
1 = 1%
38.06
U/f curve freq3
Defines the frequency at the 3rd point on the custom
U/f
curve in percent of parameter
1 … 500%
3rd point, frequency.
1 = 1%
38.07
U/f curve freq4
Defines the frequency at the 4th point on the custom
U/f
curve in percent of parameter
1 … 500%
4th point, frequency.
1 = 1%
38.08
U/f curve freq5
Defines the frequency at the 5th point on the custom
U/f
curve in percent of parameter
1 … 500%
5th point, frequency.
1 = 1%
38.09
U/f curve volt1
Defines the voltage at the 1st point on the custom
U/f
curve
in percent of parameter
0 … 200%
1st point, voltage.
1 = 1%
38.10
U/f curve volt2
Defines the voltage at the 2nd point on the custom
U/f
curve
in percent of parameter
0 … 200%
2nd point, voltage.
1 = 1%
38.11
U/f curve volt3
Defines the voltage at the 3rd point on the custom
U/f
curve
in percent of parameter
0 … 200%
3rd point, voltage.
1 = 1%
38.12
U/f curve volt4
Defines the voltage at the 4th point on the custom
U/f
curve
in percent of parameter
0 … 200%
4th point, voltage.
1 = 1%
38.13
U/f curve volt5
Defines the voltage at the 5th point on the custom
U/f
curve
in percent of parameter
0 … 200%
5th point, voltage.
1 = 1%
38.16
Flux ref pointer
Selects the source of the flux reference.
Pointer
Value pointer setting (see
on page
-
40
40 Motor control
Motor control settings such as performance/noise
optimization, slip gain, voltage reserve and IR
compensation.
40.01
Motor noise
An optimization setting for balancing between control
performance and motor noise level.
Cyclic
Control performance optimized for cyclic load applications.
Note:
With this setting, the maximum motor cable length is
smaller than with
0
Low noise
Minimizes motor noise; control performance optimized for
high (> 300 Hz) output frequencies.
Note:
Drive loadability is reduced with this setting and some
derating must be applied if a certain constant output current
is needed. This setting is not recommended for cyclic load
applications. The maximum motor cable length is 50 m
(164 ft) with drives up to 45 kW.
1
Default
Control performance optimized for long motor cables.
2
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...