![ABB ACQ810 Скачать руководство пользователя страница 64](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549064.webp)
64 Program features
Protective functions
Pressure monitoring
The control program contains protective functions for two-level analog or single-level
digital pressure monitoring of both the inlet and outlet of the pump.
In analog monitoring, whenever the pressure being monitored meets the first limit, the
drive indicates a warning, trips on a fault, or starts to follow a pre-defined reference.
When the second limit is met, the drive either stops or trips on a fault.
In digital pressure monitoring, one limit is observed. Whenever the limit is met, the
drive indicates an alarm, trips on a fault, or starts to follow a pre-defined reference.
Flow monitoring
The control program has a monitoring function for flow that can be configured to
generate an alarm or a fault whenever the flow falls below or rises above predefined
limits.
The flow can either be calculated or measured using a flow meter connected to, for
example, an analog input.
Application profile monitoring
The application profile monitoring function can be used for long-term supervision of
an actual signal. If the selected signal remains above the supervision limit for a
specified time, an alarm is generated.
For example, monitoring the deviation between the PID controller setpoint and actual
value (parameter
) gives an indication of the general condition
of the pump, piping and valves. On the other hand, the PID controller output
(parameter
) remaining at 100% for a long time would indicate
a leak in the outlet piping.
Settings
Parameter group
(page
Diagnostics
(page
(page
)
and
(page
).
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...