![ABB ACQ810 Скачать руководство пользователя страница 178](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549178.webp)
178 Parameters
23.03
Derivation time
Defines the derivation time of the speed controller.
Derivative action boosts the controller output if the error
value changes. The longer the derivation time, the more the
speed controller output is boosted during the change. If the
derivation time is set to zero, the controller works as a PI
controller, otherwise as a PID controller. The derivation
makes the control more responsive for disturbances.
The speed error derivative must be filtered with a low pass
filter to eliminate disturbances.
The figure below shows the speed controller output after an
error step when the error remains constant.
0.000 … 10.000 s
Derivation time for speed controller.
1000 = 1 s
23.04
Deriv filt time
Defines the derivation filter time constant. See parameter
0.0 … 1000.0 ms
Derivation filter time constant.
10 = 1 ms
No.
Name/Value
Description
FbEq
Gain = K
p
= 1
T
I
= Integration time > 0
T
D
= Derivation time > 0
T
s
= Sample time period = 250 µs
Δ
e = Error value change between two samples
K
p
×
T
D
×
Δ
e
T
s
Controller output
e = Error value
Error value
Time
T
I
K
p
× e
K
p
× e
%
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...