Parameters 201
31.13
Mot nom tempRise
Defines the temperature rise of the motor when the motor is
loaded with nominal current. See the motor manufacturer's
recommendations.
The temperature rise value is used by the motor thermal
protection model when parameter
is set
0 … 300 °C
Temperature rise.
1 = 1 °C
31.14
Mot therm time
Defines the thermal time constant for the motor thermal
protection model (i.e. time inside which the temperature has
reached 63% of the nominal temperature). See the motor
manufacturer's recommendations.
The motor thermal protection model is used when parameter
is set to
.
100 … 10000 s
Motor thermal time constant.
1 = 1 s
No.
Name/Value
Description
FbEq
Motor nominal
temperature rise
Temperature
Time
Ambient temperature
100%
63%
100%
Time
Time
Motor thermal time
Motor load
Temperature rise
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...