![ABB ACQ810 Скачать руководство пользователя страница 183](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549183.webp)
Parameters 183
23.20
PI tune mode
Activates the speed controller autotune function.
The autotune will automatically set parameters
and
. If the
autotune mode is chosen, also
is automatically set.
The status of the autotune routine is shown by parameter
.
WARNING!
The motor will reach the torque and
current limits during the autotune routine. ENSURE
THAT IT IS SAFE TO RUN THE MOTOR BEFORE
PERFORMING THE AUTOTUNE ROUTINE!
Notes:
• Before using the autotune function, the following
parameters should be set:
• All parameters adjusted during the start-up as
described in the
ACQ810-04 drive modules Start-up
Guide
•
•
•
• Speed reference ramp settings in group
•
• The drive must be in local control mode and stopped
before an autotune is requested.
• After requesting an autotune with this parameter, start the
drive within 20 seconds.
• Wait until the autotune routine is completed (this
parameter has reverted to the value
). The routine
can be aborted by stopping the drive.
• Check the values of the parameters set by the autotune
function.
See also section
on page
.
Done
No tuning has been requested (normal operation)
0
Smooth
Request speed controller autotune with preset settings for
smooth operation.
1
Middle
Request speed controller autotune with preset settings for
medium-tight operation.
2
Tight
Request speed controller autotune with preset settings for
tight operation.
3
User
Request speed controller autotune with the settings defined
by parameters
and
4
23.21
Tune bandwidth
Speed controller bandwidth after autotune procedure in user
mode. A larger bandwidth results in more restricted speed
controller settings.
0.00 … 2000.00 Hz
Tune bandwidth for user PI tune mode.
100 = 1 Hz
23.22
Tune damping
Speed controller damping after autotune procedure in user
mode. Higher damping results in safer and smoother
operation.
0.0 … 200.0
Speed controller damping for user PI tune mode.
10 = 1
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...