![ABB ACQ810 Скачать руководство пользователя страница 234](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549234.webp)
234 Parameters
56.06
Signal3 mode
Defines the way the signal selected by parameter
is displayed on the optional control panel.
Disabled
Signal not displayed. Any other signals that are not disabled
are shown together with their respective signal name.
-1
Normal
Shows the signal as a numerical value followed by unit.
0
Bar
Shows the signal as a horizontal bar.
1
Drive name
Shows the drive name. (The drive name can be set using the
DriveStudio PC tool.)
2
Drive type
Shows the drive type.
3
56.07
Local ref unit
Defines how speed reference is entered and displayed by
the control panel and DriveStudio PC tool. Also determines
the unit of signal
.
Note:
This parameter also applies to external control when
speed reference is given from the control panel.
rpm
Speed reference is displayed and entered in rpm.
0
Percent
Speed reference is displayed and entered in percent. The
scaling is as follows:
1
58
58 Embedded Modbus
Configuration parameters for the embedded fieldbus (EFB)
interface.
See also chapter
Control through the embedded fieldbus
58.01
Protocol ena sel
Enables/disables the embedded fieldbus communication
protocol.
Note:
When the embedded fieldbus interface is enabled, the
drive-to-drive link operation (parameter group 76) is
automatically disabled.
Disabled
Disabled.
0
Modbus RTU
Modbus RTU protocol enabled.
1
58.03
Node address
Defines the node address.
0…247
Node address.
1 = 1
58.04
Baud rate
Selects the baud rate of the RS-485 link.
4800
4.8 kbit/s.
0
9600
9.6 kbit/s.
1
19200
19.2 kbit/s.
2
38400
38.4 kbit/s.
3
57600
57.6 kbit/s.
4
76800
76.8 kbit/s.
5
No.
Name/Value
Description
FbEq
0%
Control panel
reference
Speed (rpm)
100%
-100%
0
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...