120 Parameters
No.
Name/Value
Description
FbEq
Bit
Name
Value Information
Log.
Par.
(continued)
9…10
Reserved
11
Remote
cmd
1
Fieldbus control enabled.
–
–
0
Fieldbus control disabled.
12
Ramp out
0
1
Force output of Ramp Function Generator to zero. The
drive ramps to a stop (current and DC voltage limits are
in force).
–
–
0
No action.
13
Ramp hold
1
Halt ramping (Ramp Function Generator output held).
–
–
0
No action.
14
Ramp in 0
1
Force input of Ramp Function Generator to zero.
–
–
0
No action.
15
Ext1 / Ext2
1
Switch to external control location EXT2.
OR
0
Switch to external control location EXT1.
16
Req
startinh
1
Activate start inhibit.
–
–
0
No start inhibit.
17
Local ctl
1
Request local control for Control Word. Used when the
drive is controlled from a PC tool or panel or local
fieldbus.
• Local fieldbus: Transfer to fieldbus local control
(control through Control Word or reference).
Fieldbus steals the control.
• Panel or PC tool: Transfer to local control.
–
–
0
Request external control.
18
FbLocal ref
1
Request fieldbus local control.
–
–
0
No fieldbus local control.
19…27 Reserved
28
CW B28
Freely programmable control bits. See parameters
…
–
–
29
CW B29
30
CW B30
31
CW B31
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...