Parameters 237
0…65535
No. of messages with CRC errors.
1 = 1
58.21
Raw CW LSW
Shows the LSW part of the Control Word which the drive
receives from the Modbus master. Read only.
0x0000…0xFFFF
Bits 0…15 of the Control word as a hex value.
1 = 1
58.22
Raw CW MSW
Shows the MSW part of the Control Word which the drive
receives from the Modbus master. Read only.
0x0000…0xFFFF
Bits 16…32 of the Control word as a hex value.
1 = 1
58.23
Raw SW LSW
Shows the LSW part of the Status Word which the drive
sends to the Modbus master. Read only.
0x0000…0xFFFF
Bits 0…15 of the Status word as a hex value.
1 = 1
58.24
Raw SW MSW
Shows the MSW part of the Status Word which the drive
sends to the Modbus master. Read only.
0x0000…0xFFFF
Bits 16…32 of the Status word as a hex value.
1 = 1
58.25
Raw Ref 1 LSW
Shows the LSW part of reference 1 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF
Bits 0…15 of reference 1 as a hex value.
1 = 1
58.26
Raw Ref 1 MSW
Shows the MSW part of reference 1 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF
Bits 16…32 of reference 1 as a hex value.
1 = 1
58.27
Raw Ref 2 LSW
Shows the LSW part of reference 2 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF
Bits 0…15 of reference 2 as a hex value.
1 = 1
58.28
Raw Ref 2 MSW
Shows the MSW part of reference 2 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF
Bits 16…32 of reference 2 as a hex value.
1 = 1
58.30
Transmit delay
Defines the delay time which the slave waits until it sends a
response.
0…65335 ms
Transmit delay time.
1 = 1 ms
58.31
Ret app errors
Selects whether the drive returns Modbus exception codes
or not.
No
No
0
Yes
Yes
1
58.32
Word order
Defines the order of the data words in the Modbus frame.
MSW LSW
Most significant word first, then Least significant word.
0
LSW MSW
Least significant word first, then Most significant word.
1
58.35
Data I/O 1
Defines the address of the drive parameter which the
Modbus master accesses when it reads from or writes to the
register address corresponding to Modbus In/Out parameter
no. 1. The Modbus master defines the type of the data (input
or output).
The value is conveyed in a Modbus frame using two 16-bit
words. If the drive parameter is a 16-bit value, the LSW
(Least significant word) conveys the value. If the drive
parameter is a 32-bit value, the next Modbus In/Out
parameter is also reserved.
0…9999
Parameter address. Format: xxyy, where:
xx = parameter group
yy = parameter index
1 = 1
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...