Parameters 251
76.04
Pump prior sel
Defines a source that chooses a start priority for the drive.
Two preset priorities are available: either can be selected
permanently, or a digital signal source used to switch
between the two presets.
Please note that the Autochange feature will attempt to
equalize the duty between drives with the same priority
rather than between drives with different priorities.
With a digital source,
0 = priority defined by
1 = priority defined by
Choice 1
Start priority defined by parameter
0
Choice 2
Start priority defined by parameter
1
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
76.05
Prior choice 1
Priority preset 1. See parameter
1…4
Priority preset 1.
1 = 1
76.06
Prior choice 2
Priority preset 2. See parameter
1…4
Priority preset 2.
1 = 1
76.07
Mstr loss action
If the drive is a follower, cannot find a master on the drive-to-
drive link, and is not itself allowed to be master, it will wait for
the delay specified by parameter
, then
proceed as defined by this parameter. The drive will also
generate an alarm.
Const speed
The drive continues running and adopts the speed defined
by parameter
0
Last speed
The drive continues running at the last valid reference
received from the master.
1
76.08
Mstr loss delay
Delay for a master loss situation. See parameter
0…3600 s
Delay for master loss.
1 = 1 s
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...