Parameters 169
19.07
Zero speed delay
Defines the delay for the Zero speed delay function. The
function is useful in applications where a smooth and quick
restarting is essential. During the delay, the drive knows
accurately the rotor position.
Without Zero speed delay:
The drive receives a stop command and decelerates along
a ramp. When the motor actual speed falls below the value
of
, the speed controller is switched
off. The inverter modulation is stopped and the motor coasts
to standstill.
With Zero speed delay:
The drive receives a stop command and decelerates along a
ramp. When the actual motor speed falls below the value of
, the Zero speed delay function
activates. During the delay the function keeps the speed
controller live: the inverter modulates, motor is magnetized
and the drive is ready for a quick restart.
0 … 30000 ms
Zero speed delay.
1 = 1 ms
19.08
Above speed lim
Defines the supervision limit for the actual speed.
0 … 30000 rpm
Actual speed supervision limit.
1 = 1 rpm
No.
Name/Value
Description
FbEq
Speed controller switched off:
Motor coasts to stop.
Speed
Time
Speed controller remains
active. Motor is decelerated to
true zero speed.
Speed
Time
Delay
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...