![ABB ACQ810 Скачать руководство пользователя страница 119](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549119.webp)
Parameters 119
02.36
EFB main cw
Internal Control Word of the drive received through the
embedded fieldbus interface. See chapter
the embedded fieldbus interface
on page
.
Log. = Logical combination (i.e. Bit AND/OR Selection
parameter); Par. = Selection parameter.
-
No.
Name/Value
Description
FbEq
Bit
Name
Value Information
Log.
Par.
0*
Stop
1
Stop according to the stop mode selected by par.
or according to the requested stop mode
(bits 2…6).
Note:
Simultaneous stop and start
commands result in a stop command.
OR
0
No action.
1
Start
1
Start.
Note:
Simultaneous stop and start commands
result in a stop command.
OR
0
No action.
2*
StpMode
em off
1
Emergency OFF2 (bit 0 must be 1). Drive is stopped by
cutting off motor power supply (the motor coasts to
stop). The drive will restart only with the next rising
edge of the start signal when the run enable signal is
on.
AND
–
0
No action.
3*
StpMode
em stop
1
Emergency stop OFF3 (bit 0 must be 1). Stop within
time defined by
.
AND
0
No action.
4*
StpMode
off1
1
Emergency stop OFF1 (bit 0 must be 1). Stop along the
currently active deceleration ramp.
AND
0
No action.
5*
StpMode
ramp
1
Stop along the currently active deceleration ramp.
–
0
No action.
6*
StpMode
coast
1
Coast to stop.
–
0
No action.
7
Run
enable
1
Activate run enable.
AND
0
Activate run disable.
8
Reset
0 -> 1 Fault reset if an active fault exists.
OR
other No action.
(continued)
* If all stop mode bits (2…6) are 0, stop mode is selected by parameter
. Coast
stop (bit 6) overrides the emergency stop (bits 2/3/4). Emergency stop overrides normal ramp stop
(bit 5).
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...