Parameters 267
79.16
Start stop delay
Sets a delay for stopping and starting a pump (or pumps).
Whenever a start or stop level is reached, this delay must
elapse before any action is taken.
0 … 3600 s
Start/stop delay.
1 = 1 s
79.17
Random coef
Randomizes the start levels (parameters
) to
avoid caking on the walls of the container. For example, with
this parameter set to 10.0%, the actual start level is
randomized in the range of
(start level - 10%) … (start level + 10%).
0.0 … 10.0%
Random coefficient.
TBA
79.18
Normal speed
In emptying mode, defines the pump speed when the
measured level is below the high level setting (parameter
), and the high switch (parameter
) is not active.
In filling mode, defines the pump speed when the measured
level is above the low level setting (parameter
), and
) is not active.
Ideally, this parameter should be set at the optimal operating
point of the pump.
0.0…32767.0 rpm
Normal running speed.
TBA
79.19
High speed
In emptying mode, defines the pump speed when the
measured level exceeds the level defined by parameter
, or when the high limit switch (parameter
) is active.
In filling mode, sets the pump speed when the measured
level falls below the level defined by parameter
, or when the low limit switch (parameter
) is
active.
See the diagrams at parameter
0.0…32767.0 rpm
High running speed.
TBA
80
80 Flow calculation
Settings for the flow calculation function.
See also section
on page
.
80.01
Flow calc mode
Enables the flow calculation function, and determines
whether a PQ (power/flow) curve or HQ (head/flow) curve is
used for the calculation. The curves are defined by
parameters
.
Not used
Flow calculation not used.
0
PQ curve
The PQ curve is used for flow calculation.
1
HQ curve
The HQ curve is used for flow calculation.
2
Both
Both the HQ and PQ curves are used for flow calculation.
The transition point between the curves is set by parameter
3
80.02
Pump inlet sel
Selects the analog input (or other signal source) used for
pump inlet pressure measurement.
Zero
No input selected (no pressure sensor available).
0
AI1 scaled
).
1073742341
AI2 scaled
).
1073742343
AI3 scaled
).
1073742345
AI4 scaled
(see page
).
1073742347
AI5 scaled
).
1073742349
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...