![ABB ACQ810 Скачать руководство пользователя страница 270](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549270.webp)
270 Parameters
80.15
PQ curve Q1
Flow rate (in cubic meters per hour) at point 1 on the PQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 1 of the PQ curve.
100 = 1 m
3
/h
80.16
PQ curve P2
Power input (in kilowatts) of pump at point 2 on the PQ
performance curve.
0.00 … 32767.00
kW
Power input of pump at point 2.
100 = 1 kW
80.17
PQ curve Q2
Flow rate (in cubic meters per hour) at point 2 on the PQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 2 of the PQ curve.
100 = 1 m
3
/h
80.18
PQ curve P3
Power input (in kilowatts) of pump at point 3 on the PQ
performance curve.
0.00 … 32767.00
kW
Power input of pump at point 3.
100 = 1 kW
80.19
PQ curve Q3
Flow rate (in cubic meters per hour) at point 3 on the PQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 3 of the PQ curve.
100 = 1 m
3
/h
80.20
PQ curve P4
Power input (in kilowatts) of pump at point 4 on the PQ
performance curve.
0.00 … 32767.00
kW
Power input of pump at point 4.
100 = 1 kW
80.21
PQ curve Q4
Flow rate (in cubic meters per hour) at point 4 on the PQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 4 of the PQ curve.
100 = 1 m
3
/h
80.22
PQ curve P5
Power input (in kilowatts) of pump at point 5 on the PQ
performance curve.
0.00 … 32767.00
kW
Power input of pump at point 5.
100 = 1 kW
80.23
PQ curve Q5
Flow rate (in cubic meters per hour) at point 5 on the PQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 5 of the PQ curve.
100 = 1 m
3
/h
80.24
HQ PQ brk point
Sets the transition point between the HQ and PQ
performance curves. The PQ curve is used above this
breakpoint.
0.00 … 32767.00 m
Head breakpoint between HQ and PQ curves.
100 = 1 m
80.25
Pump inlet diam
The diameter of the pump inlet in meters.
0.00 … 32767.00 m
Pump inlet diameter.
100 = 1 m
80.26
Pump outlet diam
The diameter of the pump outlet in meters.
0.00 … 32767.00 m
Pump outlet diameter.
100 = 1 m
80.27
Sensors hgt diff
Defines the height difference between the inlet and outlet
pressure sensors.
0.00 … 32767.00 m
Height difference.
100 = 1 m
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...