Fault tracing 323
0019
CURR V2 MEAS
(0x3185)
Measured offset error of V2
output phase current
measurement is too great.
(Offset value is updated
during current calibration.)
Contact your local ABB representative.
0020
CURR W2 MEAS
(0x3186)
Measured offset error of W2
output phase current
measurement is too great.
(Offset value is updated
during current calibration.)
Contact your local ABB representative.
0021
STO1 LOST
(0x8182)
Safe torque off function is
active, i.e. safety circuit
signal 1 connected between
XSTO:1 and XSTO:3 is lost.
Check safety circuit connections. For
more information, see appropriate drive
hardware manual, description of
parameter
(page
), and
Application guide - Safe torque off
function for ACSM1, ACS850 and
ACQ810 drives
(3AFE68929814
[English]).
0022
STO2 LOST
(0x8183)
Safe torque off function is
active, i.e. safety circuit
signal 2 connected between
XSTO:2 and XSTO:4 is lost.
0023
STO MODE CHANGE
(0xFF7A)
Error in changing Safe
torque off supervision, i.e.
parameter
setting could not
be changed to value
Contact your local ABB representative.
0024
INTBOARD OVERTEMP
(0x7182)
Interface board (between
power unit and control unit)
temperature has exceeded
internal fault limit.
Let drive cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
0027
PU LOST
(0x5400)
Connection between the
JCU Control Unit and the
power unit of the drive is
lost.
Check the connections between the JCU
Control Unit and the power unit.
0028
PS COMM
(0x5480)
Communication errors
detected between the JCU
Control Unit and the power
unit of the drive.
Check the connections between the JCU
Control Unit and the power unit.
0030
EXTERNAL
(0x9000)
Fault in external device.
(This information is
configured through one of
programmable digital
inputs.)
Check external devices for faults.
Check parameter
setting.
0031
SAFE TORQUE OFF
(0xFF7A)
Programmable fault:
Safe torque off function is
active, i.e. safety circuit
signal(s) connected to
connector XSTO is lost
during start or run, or while
drive is stopped and
parameter
is set to
.
Check safety circuit connections. For
more information, see appropriate drive
hardware manual, and
Application guide
- Safe torque off function for ACSM1,
ACS850 and ACQ810 drives
(3AFE68929814 [English]).
Code
Fault (fieldbus code),
other information
Cause
What to do
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...