Parameters 127
06.02
Status word2
Status word 2 of the drive.
-
No.
Name/Value
Description
FbEq
Bit
Name
Information
0
Start act
1 = Drive start command is active.
0 = Drive start command is inactive.
1
Stop act
1 = Drive stop command is active.
0 = Drive stop command is inactive.
2
Ready relay 1 = Ready to function: run enable signal on, no fault, emergency stop signal
off, no ID run inhibition. Connected by default to DIO1 by par.
.
0 = Not ready to function.
3
Modulating 1 = Modulating: IGBTs are controlled, ie. the drive is RUNNING.
0 = No modulation: IGBTs are not controlled.
4
Ref running 1 = Normal operation is enabled. Running. Drive follows the given
reference.
0 = Normal operation is disabled. Drive is not following the given reference
(eg. in magnetization phase drive is modulating).
5
Reserved
6
Off1
1 = Emergency stop OFF1 is active.
0 = Emergency stop OFF1 is inactive.
7
Start inh
mask
) start inhibit is active.
0 = No maskable start inhibit is active.
8
Start inh
nomask
1 = Non-maskable start inhibit is active.
0 = No non-maskable start inhibit is active.
9
Chrg rel
closed
1 = Charging relay is closed.
0 = Charging relay is open.
10
Sto act
1 = Safe torque off function is active. See parameter
.
0 = Safe torque off function is inactive.
11
Sleep
active
1 = Sleep mode active.
0 = Sleep mode inactive.
12
Ramp in 0
1 = Ramp Function Generator input is forced to zero.
0 = Normal operation.
13
Ramp hold 1 = Ramp Function Generator output is held.
0 = Normal operation.
14
Ramp out 0 1 = Ramp Function Generator output is forced to zero.
0 = Normal operation.
15
Reserved
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...