![ABB ACQ810 Скачать руководство пользователя страница 128](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549128.webp)
128 Parameters
06.03
Speed ctrl stat
Speed control status word.
-
06.05
Limit word1
Limit word 1.
-
No.
Name/Value
Description
FbEq
Bit
Name
Information
0
Speed act
neg
1 = Actual speed is negative.
1
Zero speed 1 = Actual speed has reached the zero speed limit (parameters
and
2
Above limit 1 = Actual speed has exceeded the supervision limit (parameter
3
At setpoint 1 = The difference between the actual speed and the unramped speed
reference is within the speed window (parameter
4
Bal active
1 = Speed controller output is being forced to value of parameter
5
PI tune
active
1 = Speed controller autotuning procedure is active.
6
PI tune
request
1 = Speed controller autotuning has been requested by parameter
7
PI tune
done
1 = Speed controller autotuning procedure has been completed
successfully.
8…15
Reserved
Bit
Name
Information
0
Torq lim
1 = Drive torque is being limited by the motor control (undervoltage control,
current control, or pull-out control), or by the torque limit parameters in
group
.
1
Spd ctl tlim
min
1 = Speed controller output minimum torque limit is active. The limit is
defined by parameter
.
2
Spd ctl tlim
max
1 = Speed controller output maximum torque limit is active. The limit is
defined by parameter
.
3…4
Reserved
5
Tlim max
speed
1 = Torque reference maximum value is limited by the rush control, because
of maximum speed limit
6
Tlim min
speed
1 = Torque reference minimum value is limited by the rush control, because
of maximum speed limit
.
7…15
Reserved
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...