Parameters 113
01.30
Polepairs
Calculated number of pole pairs in the motor.
1 = 1
01.31
Mech time const
Mechanical time constant of the drive and the machinery as
determined by the speed controller autotune function.
See parameter group
on page
1000 = 1 s
01.32
Temp phase A
Measured temperature of phase U power stage in percent of
fault limit.
10 = 1%
01.33
Temp phase B
Measured temperature of phase V power stage in percent of
fault limit.
10 = 1%
01.34
Temp phase C
Measured temperature of phase W power stage in percent of
fault limit.
10 = 1%
01.35
Saved energy
Energy saved in kWh compared to direct-on-line motor
connection.
Note:
This value is derived from subtracting the drive’s
energy consumed from the direct-on-line consumption
calculated on the basis of parameter
As such, the accuracy of this signal is dependent on the
accuracy of the direct-on-line power estimate entered in that
parameter.
See parameter group
on page
1 = 1 kWh
01.36
Saved amount
Monetary savings compared to direct-on-line motor
connection. This value is a multiplication of parameters
and
See parameter group
on page
100 = 1
01.37
Saved CO2
Reduction in CO
2
emissions in metric tons compared to
direct-on-line motor connection. This value is calculated by
multiplying the saved energy in MWh by
(default 0.5 tn/MWh).
See parameter group
on page
10 = 1 metric
ton
01.38
Temp int board
Measured temperature of the interface board in degrees
Celsius.
10 = 1 °C
02
02 I/O values
Input and output states and values; control and status words.
02.01
DI status
Status of digital inputs DI6…DI1.
Example:
000001 = DI1 is
on, DI2…DI6 are off.
-
02.02
RO status
Status of relay outputs RO5…RO1.
Example:
00001 = RO1
is energized, RO2…RO5 are de-energized.
-
02.03
DIO status
Status of digital input/outputs DIO4…DIO1.
Example:
0000001001 = DIO1 and DIO4 are on, remainder are off.
DIO3…DIO4 are available only with an FIO I/O extension
module.
-
02.04
AI1
Value of analog input AI1 in V or mA. Input type is selected
with a jumper on the JCU Control Unit.
1000 = 1 unit
02.05
AI1 scaled
Scaled value of analog input AI1. See parameters
and
.
1000 = 1 unit
02.06
AI2
Value of analog input AI2 in V or mA. Input type is selected
with a jumper on the JCU Control Unit.
1000 = 1 unit
02.07
AI2 scaled
Scaled value of analog input AI2. See parameters
and
.
1000 = 1 unit
02.08
AI3
Value of analog input AI3 in V or mA. For input type
information, see the extension module manual.
1000 = 1 unit
02.09
AI3 scaled
Scaled value of analog input AI3. See parameters
and
.
1000 = 1 unit
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...