Parameters 117
02.24
FBA main sw
Internal Status word of the drive to be sent through the
fieldbus adapter interface. See also chapter
on page
-
No.
Name/Value
Description
FbEq
Bit
Name
Value Information
0
Ready
1
Drive is ready to receive start command.
0
Drive is not ready.
1
Enabled
1
External run enable signal is received.
0
No external run enable signal is received.
2
Relay
running
1
Drive is modulating.
0
Drive is not modulating.
3
Ref
running
1
Normal operation is enabled. Drive is running and following given
reference.
0
Normal operation is disabled. Drive is not following given reference
(for example, it is modulating during magnetization).
4
Em off
(OFF2)
1
Emergency OFF2 is active.
0
Emergency OFF2 is inactive.
5
Em stop
(OFF3)
1
Emergency stop OFF3 (ramp stop) is active.
0
Emergency stop OFF3 is inactive.
6
Ack
startinh
1
Start inhibit is active.
0
Start inhibit is inactive.
7
Alarm
1
An alarm is active. See chapter
on page
0
No alarm is active.
8
At setpoint
1
Drive is at setpoint. Actual value equals reference value (i.e. the
difference between the actual speed and speed reference is within
the speed window defined by parameter
0
Drive has not reached setpoint.
(continued)
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...