Fault tracing 321
Fault messages generated by the drive
Code
Fault (fieldbus code),
other information
Cause
What to do
0001
OVERCURRENT
(0x2310)
Output current has
exceeded internal fault limit.
Check motor load.
Check acceleration times in parameter
group
.
Check motor and motor cable (including
phasing and delta/star connection).
Check that the start-up data in parameter
group 99 corresponds to the motor rating
plate.
Check that there are no power factor
correction capacitors or surge absorbers
in motor cable.
0002
DC OVERVOLTAGE
(0x3210)
Excessive intermediate
circuit DC voltage
Check that overvoltage controller is on,
parameter
Check mains for static or transient
overvoltage.
Check deceleration time.
Use coast-to-stop function (if applicable).
0003
DEVICE OVERTEMP
(0x4210)
Measured drive temperature
has exceeded internal fault
limit.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against unit power.
0004
SHORT CIRCUIT
(0x2340)
Short-circuit in motor
cable(s) or motor
Check motor and motor cable.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
0005
DC UNDERVOLTAGE
(0x3220)
Intermediate circuit DC
voltage is not sufficient due
to missing mains phase,
blown fuse or rectifier bridge
internal fault.
Check mains supply and fuses.
0006
EARTH FAULT
(0x2330)
Programmable fault:
Drive has detected load
unbalance typically due to
earth fault in motor or motor
cable.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check that there is no earth fault in motor
or motor cables:
- measure insulation resistances of motor
and motor cable.
If no earth fault can be detected, contact
your local ABB representative.
0007
FAN FAULT
(0xFF83)
Fan is not able to rotate
freely or fan is
disconnected. Fan
operation is monitored by
measuring fan current.
Check fan operation and connection.
0013
CURR MEAS GAIN
(0x3183)
Difference between output
phase U2 and W2 current
measurement gain is too
great.
Contact your local ABB representative.
0014
CABLE CROSS CON
(0x3181)
Programmable fault:
Incorrect input power and
motor cable connection (i.e.
input power cable is
connected to drive motor
connection).
Check input power connections.
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...