Parameters 185
25.05
Crit speed2 hi
Defines the high limit for critical speed range 2.
Note:
This value must be greater than or equal to the value
.
-30000 … 30000
rpm
High limit for critical speed 2.
1 = 1 rpm
25.06
Crit speed3 lo
Defines the low limit for critical speed range 3.
Note:
This value must be less than or equal to the value of
.
-30000 … 30000
rpm
Low limit for critical speed 3.
1 = 1 rpm
25.07
Crit speed3 hi
Defines the high limit for critical speed range 3.
Note:
This value must be greater than or equal to the value
.
-30000 … 30000
rpm
High limit for critical speed 3.
1 = 1 rpm
26
26 Constant speeds
Constant speed selection and values.
An active constant speed overrides the drive speed
reference. See also section
26.01
Const speed func
Determines how constant speeds are selected, and whether
the rotation direction signal is considered or not when
applying a constant speed.
No.
Name/Value
Description
FbEq
Bit
Name
Information
0
Const speed
mode
1 = Packed: 7 constant speeds are selectable using the three sources
defined by parameters
and
0 = Separate: Constant speeds 1, 2 and 3 are separately activated by
the sources defined by parameters
and
respectively.
In case of conflict, the constant speed with the smaller number takes
priority.
1
Dir ena
1 = Start dir: To determine running direction for a constant speed, the
sign of the constant speed setting (parameters
) is
multiplied by the direction signal (forward: +1, reverse: -1). For example,
if the direction signal is reverse and the active constant speed is
negative, the drive will run in the forward direction.
0 = Accord Par: The running direction for the constant speed is
determined by the sign of the constant speed setting (parameters
).
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...