68 Program features
Motor control
Constant speeds
It is possible to predefine up to 7 constant speeds. Constant speeds can be activated,
for example, through digital inputs. Constant speeds override the speed reference.
Settings
Parameter group
(page
Critical speeds
A Critical speeds function is available for applications where it is necessary to avoid
certain motor speeds or speed ranges because of, for example, mechanical
resonance problems.
Settings
Parameter group
(page
Speed controller tuning
The speed controller of the drive can be automatically adjusted using the autotune
function (parameter
). Autotuning is based on the load and inertia
of the motor and the machine. It is, however, also possible to manually adjust the
controller gain, integration time and derivation time.
Autotuning can be performed in four different ways depending on the setting of
parameter
. The selections
define how
the drive torque reference should react to a speed reference step after tuning. The
selection
will produce a slow response;
will produce a fast response.
The selection
allows customized control sensitivity adjustment through
parameters
and
. Detailed tuning status
information is provided by parameter
. If the autotuning routine
alarm will occur for approximately 15 seconds. If a stop
command is given to the drive during the autotuning, the routine is aborted.
The prerequisites for performing the autotune routine are:
• The ID run has been successfully completed
• Speed, torque, current and acceleration limits (parameter groups
) are set
• Speed feedback filtering, speed error filtering and zero speed are set (parameter
groups
and
)
• The drive is stopped.
The results of the autotune routine are automatically transferred into parameters
•
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...