330 Control through the embedded fieldbus interface
System overview
The drive can be connected to an external control system through a serial
communication link using either a fieldbus adapter or the embedded fieldbus
interface.
The embedded fieldbus interface supports the Modbus RTU protocol. The drive
control program can receive and send cyclic data from and to the Modbus master on
10 ms time level. The actual communication speed depends on other factors as well,
such as the baud rate (a parameter setting in the drive).
The drive can be set to receive all of its control information through the fieldbus
interface, or the control can be distributed between the fieldbus interface and other
available sources, for example, digital and analogue inputs.
XD2D
...
1
T
Termination
ON
JCU Drive 1
B
2
A
3
BG
N
D
XD2D
1
Termination
OFF
JCU Drive 2
B
2
A
3
BG
N
D
T
XD2D
1
T
Termination
ON
JCU Drive n
B
2
A
3
BGN
D
Process I/O (cyclic)
Service messages (acyclic)
Data flow
Control word (CW)
References
Status word (SW)
Actual values
Parameter R/W
requests/responses
Fieldbus controller
Fieldbus
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...