266 Parameters
79.08
Start 3 level
Defines the start level for pump 3. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 3.
TBA
79.09
Start 4 level
Defines the start level for pump 4. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 4.
TBA
79.10
Start 5 level
Defines the start level for pump 5. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 5.
TBA
79.11
Start 6 level
Defines the start level for pump 6. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 6.
TBA
79.12
Start 7 level
Defines the start level for pump 7. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 7.
TBA
79.13
Start 8 level
Defines the start level for pump 8. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 8.
TBA
79.14
High level
In emptying mode, when the measured level exceeds this
value, all pumps start running at the speed defined by
parameter
In filling mode, when the measured level exceeds this value,
all pumps stop (if not stopped already).
0.00 … 32768.00%
High level.
TBA
79.15
High switch
Selects a digital source that is used to determine that the
liquid level in the container has risen very high. When the
source switches on, an alarm,
is given. The
alarm is cleared when the source switches off.
Not used
No high switch used.
0
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
).
-
Pointer
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...