![ABB ACQ810 Скачать руководство пользователя страница 320](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549320.webp)
320 Fault tracing
2212
DATE WRONG
b11
b12
Date has not been set.
Set the date and time (page
2215
BOOSTING
b14
b15
Sleep boost is active.
Informative alarm.
2216
PIPE FILLING
b15
b16
The soft pipefill function is
being performed.
Informative alarm.
2217
NO MORE PUMPS
b0
b17
No further pumps are
available for starting.
Check that all appropriate pumps are
switched on.
2218
CLEANING
b1
A pump cleaning sequence
is in progress.
Informative alarm.
2219
AUTOCHANGE
b2
b18
The Autochange function is
being performed.
Informative alarm.
2220
SLEEPING
b3
b19
The drive has entered sleep
mode.
Informative alarm.
2221
START DELAY
b4
b20
A pump will start after the
start delay has elapsed.
Informative alarm.
2222
LC TANK FULL
b5
b23
The level of the liquid in the
container is very high (the
source selected by
parameter
is 1).
Informative alarm.
2223
LC TANK EMPTY
b6
b24
The level of the liquid in the
container is very low (the
source selected by
parameter
is 1).
Informative alarm.
2224
MF MASTER LOST
b7
b21
The drive cannot detect a
master on the drive-to-drive
link, and is not itself allowed
to become master.
Check that there are drives on the drive-
to-drive link that are allowed to become
master.
Check the wiring of the drive-to-drive link.
2225
MF NO SHARED DATA
b8
b25
Shared signals not
received.
Check that at least one drive has signal
sharing enabled (parameter
).
Check the status, communication
settings and wiring of the drive that is
sharing its signals.
2400
SOLUTION ALARM
(0x6F80)
b1
Alarm generated by custom
application program.
Check custom application program.
Code
Alarm (fieldbus code),
other information
Cause
What to do
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...