112 Parameters
Parameter listing
No.
Name/Value
Description
FbEq
01
01 Actual values
Basic signals for monitoring of the drive.
01.01
Motor speed rpm
Filtered, estimated motor speed in rpm. The filter time
constant can be adjusted using parameter
.
100 = 1 rpm
01.02
Motor speed %
Actual speed in percent of the motor synchronous speed.
100 = 1%
01.03 Output frequency
Estimated drive output frequency in Hz.
100 = 1 Hz
01.04
Motor current
Measured motor current in A.
100 = 1 A
01.05
Motor current %
Motor current in percent of the nominal motor current.
10 = 1%
01.06
Motor torque
Motor torque in percent of the nominal motor torque. See
also parameter
.
10 = 1%
01.07
Dc-voltage
Measured intermediate circuit voltage.
100 = 1 V
01.14
Motor speed est
Estimated motor speed in rpm.
100 = 1 rpm
01.15
Temp inverter
Estimated IGBT temperature in percent of fault limit.
10 = 1%
01.17
Motor temp1
Measured temperature of motor 1 in degrees Celsius when a
KTY sensor is used. (With a PTC sensor, the value is always
0.)
10 = 1 °C
01.18
Motor temp2
Measured temperature of motor 2 in degrees Celsius when a
KTY sensor is used. (With a PTC sensor, the value is always
0.)
10 = 1 °C
01.19
Used supply volt
Either the user-given supply voltage (parameter
), or, if auto-identification is enabled by
parameter
, the automatically
determined supply voltage.
10 = 1 V
01.21
Cpu usage
Microprocessor load in percent.
1 = 1%
01.22
Power inu out
Drive output power in kW or hp, depending on setting of
parameter
.
100 = 1 kW
or hp
01.23
Motor power
Measured motor shaft power in kW or hp, depending on
setting of parameter
.
100 = 1 kW
or hp
01.24
kWh inverter
Amount of energy that has passed through the drive (in
either direction) in kilowatt-hours. Can be reset by entering a
0 using the DriveStudio PC tool.
1 = 1 kWh
01.25
kWh supply
Amount of energy that the drive has taken from the AC
supply in kilowatt-hours. Can be reset by entering a 0 using
the DriveStudio PC tool.
1 = 1 kWh
01.26
On-time counter
On-time counter. The counter runs when the drive is
powered. Can be reset by entering a 0 using the DriveStudio
PC tool.
1 = 1 h
01.27
Run-time counter
Motor run-time counter. The counter runs when the inverter
modulates. Can be reset by entering a 0 using the
DriveStudio PC tool.
Note:
The drive logic uses this value for equalization of
pump running duties. See section
(page
).
1 = 1 h
01.28
Fan on-time
Running time of the drive cooling fan. Can be reset by
entering a 0 using the DriveStudio PC tool.
1 = 1 h
01.29
Torq nom scale
Nominal torque which corresponds to 100%.
Note:
This value is copied from parameter
if entered. Otherwise the value is calculated.
1000 =
1 N•m
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...