![ABB ACQ810 Скачать руководство пользователя страница 196](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549196.webp)
196 Parameters
30.05
Earth fault
Selects how the drive reacts when an earth fault or current
unbalance is detected in the motor or the motor cable.
No
No action taken.
0
Warning
.
1
Fault
.
2
30.06
Suppl phs loss
Selects how the drive reacts when a supply phase loss is
detected.
No
No action taken.
0
Fault
1
30.07
Sto diagnostic
Selects how the drive reacts when it detects the absence of
one or both Safe torque off (STO) signals.
Note:
This parameter is for supervision only. The Safe
torque off function can activate even when this parameter is
set to
.
For general information on the Safe torque off function, see
the
Hardware manual
of the drive, and
Application guide -
Safe torque off function for ACSM1, ACS850 and ACQ810
drives
(3AFE68929814 [English]).
Fault
The drive trips on
both of the STO signals are lost.
1
Alarm
Drive running:
The drive trips on
both of the STO signals are lost.
Drive stopped:
The drive generates a
alarm
if both STO signals are absent. If only one of the signals is
lost, the drive trips on
.
2
No
Drive running:
The drive trips on
both of the STO signals are lost.
Drive stopped:
No action if both STO signals are absent. If only one of the
signals is lost, the drive trips on
.
3
Only Alarm
The drive generates a
alarm
if both STO signals are absent. If only one of the signals is
lost, the drive trips on
.
4
30.08
Cross connection
Selects how the drive reacts to incorrect input power and
motor cable connection (i.e. input power cable is connected
to drive motor connection).
No
No action taken.
0
Fault
1
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...