322 Fault tracing
0015
SUPPLY PHASE
(0x3130)
Programmable fault:
Intermediate circuit DC
voltage is oscillating due to
missing input power line
phase or blown fuse.
Check input power line fuses.
Check for input power supply imbalance.
0016
MOTOR PHASE
(0x3182)
Programmable fault:
Motor circuit fault due to
missing motor connection
(all three phases are not
connected).
Connect motor cable.
0017
ID-RUN FAULT
(0xFF84)
Motor ID run is not
completed successfully.
Check the fault logger for a fault code
extension. See appropriate actions for
each extension below.
Extension: 1
The ID run cannot be
completed because the
maximum current setting
and/or internal current limit
of the drive is too low.
Check setting of parameters
Make sure that
>
Check that the drive is dimensioned
correctly according to the motor.
Extension: 2
The ID run cannot be
completed because the
maximum speed setting
and/or calculated field
weakening point is too low.
Check setting of parameters
,
,
. Make sure
that
•
> (0.55 ×
) > (0.50 × synchronous
speed),
•
< 0, and
• supply voltage > (0.66 ×
).
Extension: 3
The ID run cannot be
completed because the
maximum torque setting is
too low.
Check setting of parameter
and torque limits defined in
parameter group
. Make sure
that the active maximum torque (selected
by
) > 100%.
Extension: 4
Current measurement
calibration did not finish
within reasonable time.
Contact your local ABB representative.
Extension: 5…8
Internal error.
Contact your local ABB representative.
Extension: 9
Asynchronous motors only:
Acceleration did not finish
within reasonable time.
Contact your local ABB representative.
Extension: 10
Asynchronous motors only:
Deceleration did not finish
within reasonable time.
Contact your local ABB representative.
Extension: 11
Asynchronous motors only:
Speed dropped to zero
during ID run.
Contact your local ABB representative.
Extension: 14…16
Internal error.
Contact your local ABB representative.
0018
CURR U2 MEAS
(0x3184)
Measured offset error of U2
output phase current
measurement is too great.
(Offset value is updated
during current calibration.)
Contact your local ABB representative.
Code
Fault (fieldbus code),
other information
Cause
What to do
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...