Parameters 269
80.07
HQ curve H2
Head (in meters) at point 2 of the HQ performance curve.
0.00 … 32767.00 m
Head at point 2 of the HQ curve.
100 = 1 m
80.08
HQ curve Q3
Flow rate (in cubic meters per hour) at point 3 of the HQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 3 of the HQ curve.
100 = 1 m
3
/h
80.09
HQ curve H3
Head (in meters) at point 3 of the HQ performance curve.
0.00 … 32767.00 m
Head at point 3 of the HQ curve.
100 = 1 m
80.10
HQ curve Q4
Flow rate (in cubic meters per hour) at point 4 of the HQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 4 of the HQ curve.
100 = 1 m
3
/h
80.11
HQ curve H4
Head (in meters) at point 4 of the HQ performance curve.
0.00 … 32767.00 m
Head at point 4 of the HQ curve.
100 = 1 m
80.12
HQ curve Q5
Flow rate (in cubic meters per hour) at point 5 of the HQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 5 of the HQ curve.
100 = 1 m
3
/h
80.13
HQ curve H5
Head (in meters) at point 5 of the HQ performance curve.
0.00 … 32767.00 m
Head at point 5 of the HQ curve.
100 = 1 m
80.14
PQ curve P1
Power input (in kilowatts) of pump at point 1 on the PQ
performance curve.
Parameters
…
define the PQ performance curve
of the pump for the flow calculation function. The P (power
input) and Q (flow rate) coordinates of five points on the
curve are entered. The values are provided by the pump
manufacturer. All points defined should lie within the
practical operating range of the pump.
Below is an example of an PQ performance curve. The
defining parameters of the first and last points are shown.
0.00 … 32767.00
kW
Power input of pump at point 1.
100 = 1 kW
No.
Name/Value
Description
FbEq
P [kW]
Q [m
3
/h]
2
4
5
3
1
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...