346 Control through the embedded fieldbus interface
Modbus register addresses for the ABB Drives classic profile
The table below shows the Modbus register addresses for the drive data with the
ABB Drives classic profile. This profile provides a converted 16-bit access to the drive
data.
Note:
Only the least significant 16-bits of drive 32-bit control and status words can be
accessed.
Register Address
Register Data (16-bit)
400001
Fieldbus control word (CW). See section
on page
.
400002
Fieldbus reference 1 (REF1)
400003
Fieldbus reference 2 (REF2
400004
Fieldbus status word (SW). See section
on page
.
400005
Fieldbus actual value 1 (ACT1)
400006
Fieldbus actual value 2 (ACT2)
400007
Fieldbus data in/out 1 (Drive parameter
…
…
400030
Fieldbus data in/out 24 (Drive Parameter
400101
…
409999
Register address (16-bit drive parameter) = 100
×
group +
index
Example: Modbus register address to drive parameter 03.18 is
100
×
3 + 18 = 400318
Drive parameter access (32-bit drive parameter) = 200
×
group + 2
×
index
Example: Modbus register address to drive parameter 01.27
200
×
1 + 2
×
27 = 420254
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...