60 Program features
Settings
Parameter group
(page
).
Diagnostics
(page
(page
),
(page
) and
).
Soft pipefill
Filling up an empty system using normal PID control would cause a sudden pressure
peak. To avoid this, a soft pipefill function is available. This involves running the pump
at a lower speed until a predefined threshold of process actual value (for example,
measured pressure) is achieved. If a specified increase in the actual value is not
achieved within a specified time, pump speed is stepped up. This is repeated until the
Wake-up level
(
t
<
t
sd
Signal selected by
(for example, motor speed)
Selected process
actual value
STOP
t
sd
= Sleep delay (
)
Sleep level
(
START
Wake-up delay
(
t
sd
Setpoint
Time
Sleep boost step (
Control panel:
SLEEPING
Sleep boost time (
Control panel:
BOOSTING
Time
Time
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...