Parameters 161
SpRef used
).
1073742598
TorqRef used
(see page
1073742606
Proc PID out
(see page
).
1073742853
Process act%
1073742870
Pointer
Value pointer setting (see
on page
-
15.08
AO2 filt time
Defines the filtering time constant for analog output AO2.
See parameter
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
15.09
AO2 out max
Defines the maximum output value for analog output AO2.
-10.000 … 10.000 V
Maximum AO2 output value.
1000 = 1 V
15.10
AO2 out min
Defines the minimum output value for analog output AO2.
-10.000 … 10.000 V
Minimum AO2 output value.
1000 = 1 mA
15.11
AO2 src max
Defines the real value of the signal (selected by parameter
) that corresponds to the maximum AO2
output value (defined by parameter
).
-32768.000 …
32768.000
Real signal value corresponding to maximum AO2 output
value.
1000 = 1
No.
Name/Value
Description
FbEq
I
AO2
(V)
Signal
(real)
selected by par.
I
AO2
(V)
Signal
(real)
selected by par.
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...