252 Parameters
76.09
Start order corr
Whenever the application requires more pumping volume,
additional drives are started. The starting order is dependent
on the priority setting of the drive (parameters
). Whenever several drives have the same
priority, the one with the lowest node number (parameter
) is started first by default.
The Autochange function can be used to automatically rotate
the starting order within each priority group. Drives running
before the Autochange may continue to run so that the new
starting order cannot be applied immediately; this parameter
defines the method with which the drive order of priority is
corrected.
Example:
One pump is running. If necessary, additional pumps are
started in the following order:
While there is constant flow demand (and a pump must be
running), the Autochange function is activated, rotating the
starting order within each priority. After Autochange, the
order is as follows:
The desired order, however, is this:
The selections of this parameter define how the desired
order is achieved.
Optimal
Drive order of priority is corrected only when the number of
drives needs to be increased or decreased by the master as
required by the process.
0
Instant chng
Drive order of priority is corrected as soon as a new starting
order is generated, for example when the Autochange
conditions are met. The order is corrected by stopping low-
priority drives. Higher-priority drives are then started as
required by the process.
1
76.10
Master location
Defines whether the master status is passed on with each
started drive or not.
Stable
The first drive started will remain the master as long as
possible, until, for example, the drive is no longer allowed to
be master (by parameter
), or the drive
trips on a fault.
0
No.
Name/Value
Description
FbEq
ID: 1
Priority: 1
ID: 2
Priority: 1
ID: 3
Priority: 2
ID: 4
Priority: 2
+
+
+
Running
Flow demand
ID: 2
Priority: 1
ID: 1
Priority: 1
ID: 4
Priority: 2
ID: 2
Priority: 2
+
+
+
Running
Flow demand
ID: 2
Priority: 1
ID: 1
Priority: 1
ID: 4
Priority: 2
ID: 2
Priority: 2
+
+
+
Flow demand
Running
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...