![ABB ACQ810 Скачать руководство пользователя страница 316](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549316.webp)
316 Fault tracing
2035
PS COMM
(0x5480)
b3
Communication errors
detected between the JCU
Control Unit and the power
unit of the drive.
Check the connections between the JCU
Control Unit and the power unit.
2036
RESTORE
(0x6300)
b4
Restoration of backed-up
parameters failed.
Contact your local ABB representative.
2037
CUR MEAS
CALIBRATION
(0x2280)
b5
Current measurement
calibration will occur at next
start.
Informative alarm.
2039
EARTH FAULT
(0x2330)
b7
Programmable alarm:
Drive has detected load
unbalance typically due to
earth fault in motor or motor
cable.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable.
If no earth fault can be detected, contact
your local ABB representative.
2040
AUTORESET
(0x6080)
b8
A fault is to be autoreset.
Informative alarm. See parameter group
.
2041
MOTOR NOM VALUE
(0x6383)
b9
The motor configuration
parameters are set
incorrectly.
Check the settings of the motor
configuration parameters in group 99.
The drive is not
dimensioned correctly.
Check that the drive is sized correctly for
the motor.
2043
STALL
(0x7121)
b11
Programmable alarm:
Motor is operating in stall
region because of e.g.
excessive load or
insufficient motor power.
Check motor load and drive ratings.
Check fault function parameters.
2044
LCURVE
(0x2312)
b12
Programmable alarm:
/
Overload or underload limit
has been exceeded.
Check the settings of the parameters in
group
.
2045
LCURVE PAR
(0x6320)
b13
The load curve has been
incorrectly or inconsistently
defined.
Check the settings of the parameters in
group
.
2046
FLUX REF PAR
(0x6320)
b14
The
U/f
(voltage/frequency)
curve has been incorrectly
or inconsistently defined.
Check the settings of the parameters in
group
.
2048
OPTION COMM LOSS
(0x7000)
b0
Communication between
drive and option module
(FEN-xx and/or FIO-xx) is
lost.
Check that option modules are properly
connected to Slot 1 (or) Slot 2.
Check that option modules or Slot 1/2
connectors are not damaged. To
determine whether module or connector
is damaged: Test each module
individually in Slot 1 and Slot 2.
Code
Alarm (fieldbus code),
other information
Cause
What to do
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...