282 Parameters
Internal 24V
The drive control unit is powered from the drive power unit it
is mounted on. This is the default setting.
0
External 24V
The drive control unit is powered from an external power
supply.
1
95.03
Temp inu ambient
Defines the maximum ambient temperature. This
temperature is used to calculate the estimated drive
temperature. If the measured drive temperature exceeds the
estimated value, an alarm
)
or fault
(
)
is generated.
0…55 °C
Drive ambient temperature.
1 = 1 °C
97
97 User motor par
Motor values supplied by the user that are used in the motor
model.
97.01
Use given params
Activates the motor model parameters
.
Notes:
Parameter value is automatically set to zero when ID run is
selected by parameter
. The values of
are updated according to the
motor characteristics identified during the ID run.
This parameter cannot be changed while the drive is
running.
NoUserPars
inactive.
0
UserMotPars
are used in the
motor model.
1
UserPosOffs
Reserved.
2
AllUserPars
Reserved.
3
97.02
Rs user
Defines the stator resistance
R
S
of the motor model.
0.00000 … 0.50000
p.u.
Stator resistance in per unit.
100000 =
1 p.u.
97.03
Rr user
Defines the rotor resistance
R
R
of the motor model.
0.00000 … 0.50000
p.u.
Rotor resistance in per unit.
100000 =
1 p.u.
97.04
Lm user
Defines the main inductance
L
M
of the motor model.
0.00000 …
10.00000 p.u.
Main inductance in per unit.
100000 =
1 p.u.
97.05
SigmaL user
Defines the leakage inductance
σ
L
S
.
0.00000 … 1.00000
p.u.
Leakage inductance in per unit.
100000 =
1 p.u.
97.09
Rs user SI
Defines the stator resistance
R
S
of the motor model.
0.00000 …
100.00000 ohm
Stator resistance.
100000 =
1 ohm
97.10
Rr user SI
Defines the rotor resistance
R
R
of the motor model.
0.00000 …
100.00000 ohm
Rotor resistance.
100000 =
1 ohm
97.11
Lm user SI
Defines the main inductance
L
M
of the motor model.
0.00 …100000.00
mH
Main inductance.
100 = 1 mH
97.12
SigL user SI
Defines the leakage inductance
σ
L
S
.
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...