Fault tracing 325
0056
TECH LIB CRITICAL
(0x6382)
Permanent fault generated
by a technology library.
Refer to the documentation of the
technology library.
0057
FORCED TRIP
(0xFF90)
Generic Drive
Communication Profile trip
command.
Check PLC status.
0058
FB PAR ERROR
(0x6320)
The drive does not have a
functionality requested by
PLC, or requested
functionality has not been
activated.
Check PLC programming.
Check settings of parameter group
.
0059
STALL
(0x7121)
Programmable fault:
Motor is operating in stall
region because of e.g.
excessive load or
insufficient motor power.
Check motor load and drive ratings.
Check fault function parameters.
0060
LOAD CURVE
(0x2312)
Programmable fault:
Overload or underload limit
has been exceeded.
Check the settings of the parameters in
group
0063
MOTOR TEMP2
(0x4313)
Programmable fault:
Estimated motor
temperature (based on
motor thermal model) has
exceeded fault limit defined
by parameter
.
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
Check motor thermal model settings
(parameters
…
).
Measured motor
temperature has exceeded
fault limit defined by
parameter
.
Check that actual number of sensors
corresponds to value set by parameter
.
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
0064
IGBT OVERLOAD
(0x5482)
Excessive IGBT junction to
case temperature. This fault
protects the IGBT(s) and
can be activated by a short
circuit in the motor cable.
Check motor cable.
0065
IGBT TEMP
(0x4210)
Drive IGBT temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
0066
COOLING
(0x4290)
Drive module temperature is
excessive.
Check setting of parameter
Check ambient temperature. If it exceeds
40 °C (104 °F), ensure that load current
does not exceed derated load capacity of
drive. See appropriate
Hardware Manual.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
Code
Fault (fieldbus code),
other information
Cause
What to do
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...