Parameters 229
49.06
Data storage6
Data storage parameter 6.
-2147483647 …
2147483647
32-bit data.
1 = 1
49.07
Data storage7
Data storage parameter 7.
-2147483647 …
2147483647
32-bit data.
1 = 1
49.08
Data storage8
Data storage parameter 8.
-2147483647 …
2147483647
32-bit data.
1 = 1
50
50 Fieldbus
Settings for configuration of communication via a fieldbus
adapter.
See also chapter
Control through a fieldbus adapter
on page
50.01
FBA enable
Enables communication between the drive and fieldbus
adapter.
Disable
Communication between the drive and fieldbus adapter
disabled.
0
Enable
Communication between the drive and fieldbus adapter
enabled.
1
50.02
Comm loss func
Selects how the drive reacts upon a fieldbus communication
break. The time delay is defined by parameter
.
No
Communication break detection disabled.
0
Fault
Communication break detection active. Upon a
communication break, the drive trips on fault
and coasts to stop.
1
Spd ref Safe
Communication break detection active. Upon a
communication break, the drive generates alarm
and sets the speed to the value defined by
parameter
.
WARNING
! Make sure that it is safe to continue
operation in case of a communication break.
2
Last speed
Communication break detection active. Upon a
communication break, the drive generates alarm
and freezes the speed to the level the drive
was operating at. The speed is determined by the average
speed over the previous 10 seconds.
WARNING
! Make sure that it is safe to continue
operation in case of a communication break.
3
50.03
Comm loss t out
Defines the time delay before the action defined by
parameter
is taken. Time count starts
when the link fails to update the message.
0.3 … 6553.5 s
Time delay.
10 = 1 s
50.04
FBA ref1 modesel
Selects the fieldbus reference FBA REF1 scaling and the
actual value, which is sent to the fieldbus (FBA ACT1).
Raw data
No scaling (i.e. data is transmitted without scaling). Source
for the actual value, which is sent to the fieldbus, is selected
by parameter
0
1
Reserved.
1
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...