![ABB ACQ810 Скачать руководство пользователя страница 315](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549315.webp)
Fault tracing 315
2008
ID-RUN
(0xFF84)
Motor identification run is
on.
This alarm belongs to normal start-up
procedure. Wait until drive indicates that
motor identification is completed.
Motor identification is
required.
This alarm belongs to normal start-up
procedure.
Select how motor identification should be
performed, parameter
Start identification routines by pressing
Start key.
2009
EMERGENCY STOP
(0xF081)
Drive has received
emergency stop command
(OFF1/OFF3).
Check that it is safe to continue
operation.
Return emergency stop push button to
normal position (or adjust the fieldbus
Control Word accordingly).
Restart drive.
2013
DEVICE OVERTEMP
(0x4210)
b13
Measured drive temperature
has exceeded internal alarm
limit.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against unit power.
2014
INTBOARD OVERTEMP
(0x7182)
b14
Interface board (between
power unit and control unit)
temperature has exceeded
internal alarm limit.
Let drive cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
2017
FIELDBUS COMM
(0x7510)
Cyclical communication
between drive and fieldbus
adapter module or between
PLC and fieldbus adapter
module is lost.
Check status of fieldbus communication.
See appropriate User’s Manual of
fieldbus adapter module.
Check settings of parameter group
.
Check cable connections.
Check if communication master is able to
communicate.
2018
LOCAL CTRL LOSS
(0x5300)
Control panel or PC tool
selected as active control
location for drive has
ceased communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Replace control panel in mounting
platform.
2019
AI SUPERVISION
(0x8110)
An analog input has
reached limit defined by
parameter
Check analog input source and
connections.
Check analog input minimum and
maximum limit settings.
2020
FB PAR CONF
(0x6320)
The drive does not have a
functionality requested by
PLC, or requested
functionality has not been
activated.
Check PLC programming.
Check settings of parameter group
.
2021
NO MOTOR DATA
(0x6381)
Parameters in group 99
have not been set.
Check that all the required parameters in
group 99 have been set.
Code
Alarm (fieldbus code),
other information
Cause
What to do
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...