324 Fault tracing
0032
OVERSPEED
(0x7310)
Motor is turning faster than
highest allowed speed due
to incorrectly set minimum/
maximum speed,
insufficient braking torque or
changes in load when using
torque reference.
Check minimum/maximum speed
settings, parameters
.
Check adequacy of motor braking torque.
Check applicability of torque control.
0036
LOCAL CTRL LOSS
(0x5300)
Programmable fault:
Control panel or PC tool
selected as active control
location for drive has
ceased communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Replace control panel in mounting
platform.
0037
NVMEM CORRUPTED
(0x6320)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0038
OPTIONCOMM LOSS
(0x7000)
Communication between
drive and option module
(FIO-xx) is lost.
Check that option modules are properly
connected to Slot 1 and (or) Slot 2.
Check that option modules or Slot 1/2
connectors are not damaged. To
determine whether module or connector
is damaged: Test each module
individually in Slot 1 and Slot 2.
0045
FIELDBUS COMM
(0x7510)
Programmable fault:
Cyclical communication
between drive and fieldbus
adapter module or between
PLC and fieldbus adapter
module is lost.
Check status of fieldbus communication.
See appropriate User’s Manual of
fieldbus adapter module.
Check settings of parameter group
Check cable connections.
Check if communication master is able to
communicate.
0046
FB MAPPING FILE
(0x6306)
Drive internal fault
Contact your local ABB representative.
0047
MOTOR OVERTEMP
(0x4310)
Programmable fault:
Estimated motor
temperature (based on
motor thermal model) has
exceeded fault limit defined
by parameter
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
Check motor thermal model settings
(parameters
…
Measured motor
temperature has exceeded
fault limit defined by
parameter
.
Check that actual number of sensors
corresponds to value set by parameter
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
0049
AI SUPERVISION
(0x8110)
Programmable fault:
An analog input has
reached limit defined by
parameter
Check analog input source and
connections.
Check analog input minimum and
maximum limit settings.
0055
TECH LIB
(0x6382)
Resettable fault generated
by a technology library.
Refer to the documentation of the
technology library.
Code
Fault (fieldbus code),
other information
Cause
What to do
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...