![ABB ACQ810 Скачать руководство пользователя страница 353](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549353.webp)
Control through the embedded fieldbus interface 353
Modbus register addresses for the DCU 32-bit profile
The table below shows the Modbus register addresses and data with the DCU 32-bit
profile. This profile provides native 32-bit access to the drive data.
Register address
Register data (16-bit)
400001
Control word (
) – Least significant 16-bits
400002
Control word (
) – Most significant 16-bits
400003
Reference 1 (
) – Least significant 16-bits
400004
Reference 1 (
) – Most significant 16-bits
400005
Reference 2 (
) – Least significant 16-bits
400006
Reference 2 (
) – Most significant 16-bits
400007
Data in/out 1 (Drive parameter
)
...
...
400018
Data in/out 12 (Drive parameter
58.46 Data I/O 12
)
400051
Status word (LSW of
) – Least significant 16-bits
400052
Status word (MSW of
) – Most significant 16-bits
400053
Actual value 1 (selected by parameter
) – Least
significant 16-bits
400054
Actual value 1 (selected by parameter
) – Most
significant 16-bits
400055
Actual value 2 (selected by parameter
) – Least
significant 16-bits
400056
Actual value 2 (selected by parameter
) – Most
significant 16-bits
400057
Data in/out 13 (Drive parameter
58.47 Data I/O 13
)
…
…
400068
Data in/out 24 (Drive parameter
400101…409999
Register address (16-bit drive parameter) = 100
×
group +
index
Example: Modbus register address to drive parameter 03.18 is
100
×
3 + 18 = 400318
Drive parameter access (32-bit drive parameter) = 200
×
group + 2
×
index
Example: Modbus register address to drive parameter 01.27
200
×
1 + 2
×
27 = 420254
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...