![ABB ACQ810 Скачать руководство пользователя страница 214](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549214.webp)
214 Parameters
35.19
Proc var3 unit
Specifies the unit for parameter
(process
variable 3).
0…98
See parameter
1 = 1
35.20
Proc var3 max
Maximum value for process variable 3. See diagram at
parameter
-32768…32768
Maximum value for process variable 3.
1 = 1
35.21
Proc var3 min
Minimum value for process variable 3. See diagram at
parameter
-32768…32768
Minimum value for process variable 3.
1 = 1
36
36 Timed functions
Configuration of timers.
See also section
on page
.
36.01
Timers enable
Enable/disable control for timers. Whenever the source
selected by this parameter is off, timers are disabled; when
the source is on, timers are enabled.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
).
-
Pointer
36.02
Timers mode
Specifies whether the time periods defined by parameters
…
weekly.
36.03
Start time1
Defines the start time for time period 1.
00:00:00 …
24:00:00
Start time for time period 1.
1 = 1 s
(24:00:00 =
86400)
36.04
Stop time1
Defines the stop time for time period 1.
00:00:00 …
24:00:00
Stop time for time period 1.
1 = 1 s
(24:00:00 =
86400)
36.05
Start day1
Defines the week day on which time period 1 begins.
No.
Name/Value
Description
FbEq
Bit
Function
0
Timer1 mode
0 = Daily
1 = Weekly
1
Timer2 mode
0 = Daily
1 = Weekly
2
Timer3 mode
0 = Daily
1 = Weekly
3
Timer4 mode
0 = Daily
1 = Weekly
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...