328 Fault tracing
0318
MENU HIDING
Menu hiding file missing or
corrupted.
Reload application.
Contact your local ABB representative.
0401
PIPEFILL TOUT
Maximum allowed time for
the Pipefill function
exceeded.
Check the pump system.
Check parameters
.
0402
MIN FLOW
Measured flow below
minimum limit.
Check the pump system for reasons
such as leaks that might cause a loss of
measured flow.
Check parameters
.
0403
MAX FLOW
Measured flow above
maximum limit.
Check the pump system for reasons that
might cause an increase in measured
flow.
Check parameters
.
0404
LOW PRESSURE
Pressure at pump inlet too
low.
Check for a closed valve on the inlet side
of the pump.
Check piping for leaks.
0405
HIGH PRESSURE
Pressure at pump outlet too
high.
Check piping for blocks.
0406
VERY LOW PRESS
Pressure at pump inlet too
low.
Check for a closed valve on the inlet side
of the pump.
Check piping for leaks.
0407
VERY HIGH PRESS
Pressure at pump outlet too
high.
Check piping for blocks.
0408
MAX CLEANINGS
Maximum number of
cleaning sequences
exceeded (see parameter
group
).
Check for reasons that might have had
an increasing effect on the monitored
signal (parameter
). For example,
increased viscosity of the fluid, or faulty
pump bearings may increase the current
drawn by the motor, and trigger the
cleaning sequence more frequently.
0409
MF MASTER LOST
The drive cannot detect a
master on the drive-to-drive
link, and is not itself allowed
to become master.
Check that there are drives on the drive-
to-drive link that are allowed to become
master.
Check the wiring of the drive-to-drive link.
0410
MF NO SHARED DATA
Shared signals not
received.
Check that at least one drive has signal
sharing enabled (parameter
Check the status, communication
settings and wiring of the drive that is
sharing its signals.
Code
Fault (fieldbus code),
other information
Cause
What to do
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...