
276 Parameters
AI3 scaled
(see page
).
1073742345
AI4 scaled
(see page
).
1073742347
AI5 scaled
(see page
).
1073742349
Flow act
Calculated flow as indicated by
(see page
).
1073743109
Pointer
Value pointer setting (see
on page
).
-
81.19
Flow max prot
Defines the action to be taken if the flow (signal selected by
parameter
) remains above the limit
set by parameter
for longer than the
time set by parameter
.
Not sel
Maximum flow protection disabled.
0
Alarm
.
1
Fault
2
81.20
Flow max level
Defines the maximum flow limit. See parameter
.
0.00 … 32767.00
m
3
/s
Maximum flow.
100 = 1 m
3
/s
81.21
Flow min prot
Defines the action to be taken if the flow (signal selected by
parameter
) remains below the limit set
by parameter
for longer than the time
set by parameter
.
See also parameter
.
Not sel
Minimum flow protection disabled.
0
Alarm
1
Fault
2
81.22
Flow min level
Defines the minimum flow limit. See parameter
.
0.00 … 32767.00
m
3
/s
Minimum flow.
100 = 1 m
3
/s
81.23
Flow ctrl delay
Specifies a delay for minimum/maximum flow protection.
See parameters
.
0…12600 s
Delay for minimum/maximum flow protection.
1 = 1 s
81.24
Flow check delay
After starting the drive, defines a period during which the
minimum flow protection is disabled so that normal flow can
be reached.
0…12600 s
Start delay for minimum flow protection.
1 = 1 s
81.25
Appl prot ctrl
Enables/disables the Application profile protection function,
based on long-term monitoring of an internal signal. If the
selected signal exceeds (and remains above) the
supervision limit longer than the delay set by parameter
is generated
and
bit 6 set to 1.
Not used
Application profile protection disabled.
0
PID error
Signal
compared to value of
parameter
1
PID out
Signal
compared to value of
parameter
2
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...