Parameters 277
81.26
Prof limit
Supervision limit for the Application profile protection.
0.00 … 32767.00 %
Supervision limit.
100 = 1%
81.27
Prof limit dly
Delay for the Application profile protection.
0.00 … 35791394.11
h
Delay.
100 = 1 h
81.28
Pipefill enable
Enables/disables (or selects a signal source that
enables/disables) the Pipefill function when the drive is
started.
1 = Enable Pipefill function. If the signal is removed before
Pipefill is completed, Pipefill is aborted and normal PID
control enabled.
Not used
Pipefill function disabled.
0
Active
Pipefill function enabled.
1
DI1
The status of digital input DI1 (as indicated by
, bit 0) determines whether the Pipefill function is
enabled or disabled.
1073742337
DI2
The status of digital input DI2 (as indicated by
, bit 1) determines whether the Pipefill function is
enabled or disabled.
1073807873
DI3
The status of digital input DI3 (as indicated by
, bit 2) determines whether the Pipefill function is
enabled or disabled.
1073873409
DI4
The status of digital input DI4 (as indicated by
, bit 3) determines whether the Pipefill function is
enabled or disabled.
1073938945
DI5
The status of digital input DI5 (as indicated by
, bit 4) determines whether the Pipefill function is
enabled or disabled.
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
81.29
Pipefill step
Defines the speed step used for the Pipefill function, as well
as the pump speed reference immediately after the Pipefill
function is activated.
The speed step is added to the reference after the time
defined by parameter
has elapsed
and the change in process actual value defined by
parameter
has not been reached.
The PID controller reference ramp time is specified by
parameter
.
0…32767 rpm
Speed step for the Pipefill function.
1 = 1 rpm
81.30
Req act change
Defines the requested change in process actual value within
the time set by parameter
0.00 … 100.00%
Requested change.
100 = 1%
81.31
Act change delay
Defines the time that is waited after the process actual value
is compared to the previous actual value.
If parameter
is measured in the actual
value, the speed reference stays as it is. If
is not seen in the actual value, the value of
parameter
reference.
0…100 s
Delay for actual value change.
1 = 1 s
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...